TOR 110-EFP

Microprocessor device TOR 110-EFP is designed for selective protection of overhead and underground lines under single-phase earth faults (permanent and transient) and double earth faults regardless of the operation mode of the neutral, as well as for indication of the line phase current.


Warranty
Aftersales service
Implemented QMS
ISO 9001
Assistance
in eqipment selection
24/7 technical support
Trainings

Microprocessor device TOR 110-EFP fixes the direction of the transient wave transmission that occurs at the short circuit location to detect the direction of the single phase-to-earth fault. The fact of a single-phase earth fault is accompanied by the appearance of residual voltage 3U0 of power frequency, which is used to pick up the start of the device.

For substations without voltage transformers, microprocessor devices operate in the centralized protection mode against single-phase earth fault with signals exchange organization.





Device is installed on the door in the place of an ammeter or counting register.

  • Device is connected to voltage and to zero sequence current (to a core balance  current transformer (CBCT), or to the sum of phase currents).
  • Connection to the measuring circuits is monitored by the phasing control function of the device.
  • Monitoring of open delta circuits discontinuity is provided.
  • TOR 110-EFP can operate to tripping of damaged line and signalling.
  • A digital indicator shows the instantaneous values of the voltage and zero sequence current in the emergency mode (capacity current of a section).
  • A built-in disturbance recorder of a single phase-to-earth fault, and the event recorder allows to analyze the protection operation
  • Device can connect to SCADA via IEC 60870-103 protocol using communication port RS-485.
  • For signalling, there are LEDs indicating the tripping, short circuit in the forward and reverse direction, cutoff operation by zero sequence, voltage circuits failures.

Scheme of connection of the device TOR 110-EFP when performing individual protection against earth faults:


1-158.png
     Parameter      Value 
 Rated operating current voltage of power supply circuits (AC/DC), V   110/220
 Operating range of AC/DC voltage of control current of power supply circuits, V   88 ... 264
 Operating range for AC circuits, A  0,005 ... 10
 Operating range for AC voltage circuits, V   0,05 ... 120 
 Permissible overload on AC circuits  100 A for 1s
 Rated alternating voltage of measurement circuits, V  100
 Rated frequency, Hz  50
 Working temperature range, °С  -40 … +55 
 Humidity (not condensing), no more  80% at +25°С 
 Overall dimensions (without fasteners)  90 x 90 x 175 mm 
 Weight, no more, kg  1,6
     Device power consumption
 - AC voltage circuits, VA  0,07
 - AC circuits, VA  0,03   
 - control current circuits at rest / tripping, W  3,6 / 3,9
Send us a message and our engineers will promptly answer all your questions.
Send a message and our engineers will promptly answer all your questions.
Send us a message and our specialists will promptly answer all your questions.
Service support
Warranty and post-warranty service, commissioning, supervision, engineering services, service centers, design and redesign
Our advantages
In-house manufacture

Our own production line allows us to ensure high quality and short production time

Social responsibility

Our main tasks in the field of social policy are creation of decent working conditions for employees as well as assistance to orphanages and homes for the elderly

Service

Employees of the company or service centers personally carry out troubleshooting at the facility within 2–5 days (travelling time excluded)

Quality

The equipment manufactured by our company has certificates of conformity and is regularly certified


Our offices on the map
All contacts in a list
    Main office
    Representation
    Representatives